Multi core Flexible power cable with PVC insulated & PVC sheathed

Multi core Flexible power cable with PVC insulated  & PVC sheathed

Cu/PVC/PVC

NYY-J , NYY-O , H1VV-F

Rated voltage :  0.6/1 KV

Reference standard :  ISIRI 3569-1  , IEC 60502-1

Application : : For indoor or outdoor in cable duct or tray. These cable are suitable for switching boxes, industrial plants, and commercial buildings. These cables are suitable for direct burial if there is no mechanical stresses.

Construction

  1. Conductor  :  Fine stranded  plain annealed copper acc. to IEC 60228 or      ISIRI 3084  or VDE 0295 , class 5  .
  2. Insulation  :  PVC /A 
  3. Color of insulation : As request 
  4. Protective conductor : Green/Yellow (if any)
  5. Assembly : Cores twisted together ,(with filler if necessary)
  6. Inner covering : PVC
  7. Outer sheath : PVC/ST1 , PVC/YM2 , PVC/TM2 

   Technical specification

  1. Max. conductor temperature :  70 °C
  2. Conductor resistant : Refer to table (1)
  3. Test voltage : 3.5 KV AC or 8.4 KV DC  for 5 min
  4. Current carrying capacity : Refer to table  (2)
  5. Bending radius  :  Refer to table (3)
  6. Permissible short circuit temperature : 160 °C
  7. Flame retardant : ac. to  IEC 60332-1